Supplying you with customized 450/750v lszh insulated (single core), it is one of the reliable 450/750v lszh insulated (single core) manufacturers and suppliers, welcome to wholesale our products at good price from our factory.
450/750V LSZH Insulated (single core)
Application: |
The cables is mainly used in power stations, mass transit underground passenger systems, airports,petrochemical plants, hotels, hospitals, and high-rise buildings. |
Standard: |
Basic design to BS 7211 |
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test) |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free |
IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission |
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
minimum Smoke Emission |
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases |
NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
450/750V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.
Insulation: LSZH compound
COLOUR CODE
Insulation colour as per bs7671
|
with earth conductor |
without earth conductor |
2Cores |
- |
Brown,Blue |
3Cores |
Yellow/Green,Brown,Blue |
Brown,Gray,Black |
4Cores |
Yellow/Green,Brown,Gray,Black |
Brown,Gray,Black,Blue |
5Cores |
Yellow/Green,Brown,Gray,Black,Blue |
Brown,Gray,Black,Blue,Black |
above 5 Cores |
Yellow/Green,Black Numbered |
Black Numbered |
sheath colour: Black
Physical AND THERMAL PROPERTIES
Temperature range during operation: Max.90°C for XLPE
250°C in short-circuit for 5s max.
Minimum bending radius: 6 x Overall Diameter
CONSTRUCTION PARAMETERS
Conductor |
|
|||||||
No. of Core X Cross Section |
Nominal Overall Diameter Conductor |
Nominal Insulation Thickness |
Nominal Overall Diameter |
Approx. Weight |
||||
Noxmm2 |
No./mm |
mm |
mm |
kg/km |
||||
1x1.5 |
7/0.53 |
0.7 |
3.1 |
23 |
||||
1x2.5 |
7/0.67 |
0.8 |
3.7 |
25 |
||||
1x4 |
7/0.85 |
0.8 |
4.3 |
52 |
||||
1x6 |
7/1.04 |
0.8 |
4.8 |
73 |
||||
1x10 |
7/1.35 |
1.0 |
6.2 |
120 |
||||
1x16 |
7/1.70 |
1.0 |
7.2 |
180 |
||||
1x25 |
7/2.24 |
1.2 |
9.0 |
285 |
||||
1x35 |
19/1.53 |
1.2 |
10.2 |
375 |
||||
1x50 |
19/1.78 |
1.4 |
12.0 |
510 |
||||
1x70 |
19/2.14 |
1.4 |
14.0 |
720 |
||||
1x95 |
19/2.52 |
1.6 |
16.0 |
995 |
||||
1x120 |
37/2.03 |
1.6 |
18.0 |
1230 |
||||
1x150 |
37/2.25 |
1.8 |
20.0 |
1520 |
||||
1x185 |
37/2.52 |
2.0 |
22.0 |
1900 |
||||
1x240 |
61/2.25 |
2.2 |
25.0 |
2480 |
||||
1x300 |
61/2.52 |
2.4 |
28.0 |
3100 |
||||
1x400 |
61.2.85 |
2.6 |
31.5 |
3950 |
||||
1x500 |
61/3.20 |
2.8 |
35.0 |
4950 |
||||
1x630 |
127/2.52 |
2.8 |
39.0 |
6360 |
Electrical PROPERTIES Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)
Conductor crosssectional area |
Reference Method 4 (enclosed in conduit in thermally insulating wall etc) |
Reference Method 3 (enclosed in conduit on a wall or in trunking etc) |
Reference Method 1 (clipped direct) |
Reference Method 11 (on a perforated cable tray, horizontal or vertical) |
Reference Method 12 (free air) |
||||||
Horizontal flat spaced |
Vertical flat spaced |
Trefoil |
|||||||||
2 cables, single- phase a.c. or d.c. |
3 or 4 cables, 3-phase a.c. |
2 cables, single- phase a.c. or d.c |
3 or 4 cables, 3-phase a.c. |
2 cables, single- phase a.c. or d.c. flat and touching |
3 or 4 cables, 3-phase a.c. flat and touching or trefoil |
2 cables, single- phase a.c. or d.c. or flat and touching |
3 or 4 cables, 3-phase a.c. flat and touching or trefoil |
2 cables, single- phase a.c. or d.c. or 3 c ables three phase |
2 cables, single- phase a.c. or d.c. or 3 cables three phase |
3 cables, trefoil 3-phase a.c. |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
mm2 |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
1.5 |
18 |